Can the ATV312 with 3-phase input be powered up with 120 Vac, single phase for programming only?

If the ATV312 is rated for 230 Vac input you may be able to program with 120V supply power.  For the 480V and 575V rated drives, 120VAC is too low for the drive to power up the control portion.  