Technical FAQs

Ask a Question

Is there a deadfront filler plate for an NQMB** kit used in a NQ442L2 panel if the main breaker is removed and the main lugs are used?

Issue:
Is there a deadfront filler plate for an NQMB**  kit used in a NQ442L2 panel if the main breaker is removed and the main lugs are used?

Product Line:
Panelboards

Environment:
UL 67, UL 50, CSA C22.2 No.'s 20-M1989 & 94-M91, NEMA PB1, NFPA 70 Art. 408, Federal Specification W-P-115C Type 1 Class 1 , 2003 IBC, NFPA 5000, ASCE/SE17

Cause:
A change in system design and/or equipment order necessitating the conversion of a previously installed main circuit breaker panelboard to main lugs only.

Resolution:
No, the previously offered closing plate, part no. 80103-079-02, is now obsolete. The customer is now on their own to devise a suitable and acceptable closure for the opening.

 
Was this helpful?
What can we do to improve the information ?