Technical FAQs

Ask a Question

Can you get ground-fault alarm-only (without tripping) on Powerpact H, J, and L frame breakers with electronic (Micrologic) trip units?

No, you cannot get GF `alarm-only` with these breakers.  Alarm with trip is possible; the alarm has three possible indications:
-reading on the front display module or on a PC through the communication network
-system remote indicators using SDx relay with two output contacts for alarms
-Micrologic trip unit built-in LCD display

To get GF alarm-only, you would have to use an external GF relay such as Vigirex with associated sensor and indication hardware.


CTA-ID : 2061390
Was this helpful?
What can we do to improve the information ?