Technical FAQs

Ask a Question

Is a 50A main breaker available in a NQ panelboard?

Issue:
Main breaker at 50a

Product Line:
Panelboards

Environment:
NQ

Cause:
Product offering

Resolution:
No, per NEC article 230.79, the minimum main breaker needs to be at least 60A.
Was this helpful?
What can we do to improve the information ?