Are Powerpact R frame unit mount breakers available with lugs?

Product line:  
Molded case circuit breakers

Environment:  
Powerpact R-frame

Resolution:  
No, the unit mount version of the R-frame is bus connected only.  For cable connections, you can order an RLTB or RL3TB terminal pad kit (one kit for each end of the breaker).  These kits will take 8 or 9 lugs per terminal respectively.  You must use either the RLTB/RL3TB terminal pad kit or an equivalent UL listed terminal pad and bus structure in order to bring cables to this breaker.  