Technical FAQs

Ask a Question

Can the Altivar 312 drive be set up to start with a run command active or to restart without requiring the run command to be cycled in the event of a power outage?

Yes it can. If the drive is set for 2 wire control  In the IO menu, set tCC=2C and tCt=LEL.  The same logic will apply to the run reverse command.

CTA-ID : 2058049
Was this helpful?
What can we do to improve the information ?