What class overload protection does the ATV312 drive provide?

Based on this setting the drive provides class 10 overload protection.
You can set this overload parameter in the SEt menu under ITH which is based on the motors FLA setting stamped on motor name plate.
There is additional information in the Altivar 312 Programming manual.