Why are there are two different length of wire binding screws in the AL600LS52K3 kit?

Issue:
Why are there are two different length of wire binding screws in the AL600LS52K3 kit?

Product Line:
Powerpact L frame breakers

Environment:
Electrical distribution and OEM

Cause:
The instructions do not explain what to do with the second set of screws.

Resolution:
AL600LS52K3 has a wire range of 2/0 to 500 KCMIL. The longer screws are factory-installed on the lugs and the shorter ones are shipped in the kit. The shorter ones are used for higher gage wire, to prevent interference with the lug shield.  The instructions do not explain.