Technical FAQs

Ask a Question

Will a PK15GTA Equipment Ground Bar accept either solid or stranded conductors?

Yes, this ground bar will accept either solid and stranded wire. However, there is an exception if terminating two ground conductors of different sizes. If terminating a #14 CU and a #12 CU; a #12 CU and a #10 CU; a #14 CU and a #10 CU or a #10 AL and a #12 AL, stranded conductors cannot be used.


CTA-ID : 2055433
Was this helpful?
What can we do to improve the information ?