What is the coil burden or draw on an EDB34020SA?

Issue:  
What is the shunt trip's rated coil burden for a 120 Vac shunt trip on an EDB, EGB or EJB breaker?  

Product line:  
Molded case circuit breakers

Environment:  
EDB, EGB and EJB circuit breakers for NF panel with a 120 Vac shunt trip

Resolution:  
Max. current draw:  2400 mA
Coil burden:  288 VA
50 VA xfmr recommended.