Do we have an NQ panelboard with a 225A main circuit breaker with a 120 Vac shunt trip on the main?

Issue:
Do we have an NQ panelboard with a 225A main circuit breaker with a 120 Vac shunt trip on the main?

Product Line:
Panelboards sold in the United States.

Environment:
NQ panelboards.

Cause:
Selection.

Resolution:
Yes, order the NQ interior needed and main breaker kit NQMB2HJ and order JDL36225SA.  Another option would be to use JDL36225 and field installable shunt trip number S29386.