REVISION TO FAQ 2045833: ADDED VOLTAGE AND AIC RATING INFORMATION IN RESPONSE.<br /><br />What is the replacement for a PKA36125G?<br /><br />Interrupt Rating based on Voltage:<br /> 240 Vac 480 Vac 600 Vac<br />PKA 42k 25k 22k<br />

Depending on the system voltage and the required short circuit rating, it could be a PHG36125G or a PHJ36125G.
Interrupt Rating based on Voltage:
240 Vac 480 Vac 600 Vac
PHG 65k 35k 18k
PHJ 100k 65k 25k