On a NQ double tub installation, if using a Hinged Right cover such as an NC38SHR, can the tubs be mounted next to each other or is clearance required between them?

Issue:
On a NQ double tub installation, if using a Hinged Right cover such as an NC38SHR, can the tubs be mounted next to each other or is clearance required between them?

Product Line:
NQ panelboards.

Environment:
Products sold in the United States.

Cause:
Product features.

Resolution:
The cans can be installed mounted together. With any surface mount covers including the Hinged Right type, there is no need to allow for any spacing between cans.