What is the max wire size for control wire terminals for Powerpact H and J frames breakers?

Issue:
What is the max wire size for control wire terminals for Powerpact H and J frames breakers?

Product Line:
Powerpact H and J frame

Environment:
Products sold in North America

Cause:
Need control wire on a Powerpact H or J frame.

Resolution:
Each control-wire terminal has a 1/4 in. (6.3mm) male spade connector tab which allows monitoring of circuit status.

Use catalog number S37423 for H frame, and S37424 for J frame.



See instruction bulletin, 48940-233-01


CTA-ID : 2053779