Technical FAQs

Ask a Question

Are single phase main breaker I-Line panels constructed with two pole or three pole main breakers?

Issue:
Design for single phase

Product Line:
Panelboards

Environment:
I-Line

Cause:
Application
 

Resolution:
Because there are 3 poles on the busbar, main breaker I-Line panels always use 3 pole breakers, whether single phase or three phase. For single phase panels, only A and C phases are connected to the utility power. The B or center phase is used only as a spacer.


CTA-ID : 2053706

Was this helpful?
What can we do to improve the information ?