What are the correct micro-ohm readings (contact resistance) for an HVL/cc switch?

The contact life can be verified by performing a millivoltage or
micrometer test. The value should not increase by 300% of the original value
of 80 micro-ohms using a 100 A test micrometer. (Should not exceed 240 micro-ohms). NOTE: The loads may not be the same on each phase. Therefore, the contact resistance will vary on each phase.