Can you use NQMB2HJ with a 2P HDL or JDL breaker for single phase applications in a NQ panelboard?

Issue:
Can you use NQMB2HJ with a 2P HDL or JDL breaker for single phase applications in a NQ panelboard?

Product Line:
Panelboards.

Environment:
Products sold in the United States.

Cause:
Assembly/Installation

Resolution:
No, NQMB2HJ is not designed for 2P breakers, Customer will need to use a 3P breaker and wire as single phase using only the outer poles.