What are the ambient temperature limits in which SquareD/Schneider Electric LVGP Transformers can be stored or operated?

Issue:
Transformers have temperature limits for storage and operation

Product Line:
LV Transformers

Environment:
Applies to Ventilated and Non Ventilated Transformers by SquareD/Schneider Electric

Cause:
Transformers are used in various temperature environments

Resolution:

Standard SquareD/Schneider Electric Ventilated and TENV (Totally Enclosed Non-Ventilated) Transformers are designed for the ambient temperatures described below
OPERATING Temperature Range:
Minimum: -40C (-40F)
Maximum: The ambient must maintain a 24 hour average of 30C (86F) with a maximum during that time of 40C (104F)

STORAGE Temperature Range:
Minimum: -60C (-76F)
Maximum: 60C (140F)

The customer must consult SquareD/Schneider Electric  Document 43006-850-01, attached below,  for storage instructions. 


 