Technical FAQs

Ask a Question

How is the EHB breaker removed from a NEHB panel?

Issue:
How is the EHB breaker removed from a NEHB panel?

Product Line:
NEHB Panelboard, EHB Breakers

Environment:
NEHB Panelboards

Resolution:
  1. First make sure power to the panel is off and that the bus is not live.
  2. Pull the outside edge of the breaker towards you so that it comes off the mounting rail.
  3. Pull the breaker towards the wire gutter. The flexible connector will unfold and expose the screw head of the bolt.
  4. Unscrew the bolt connecting breaker to the panel.
Both NEHB Panelboards and EHB breaker are obsolete. All parts and accessories are not available.

CTA-ID : 2052828
Was this helpful?
What can we do to improve the information ?