8903LG: Can they get a 2 wire control on electrically held contactors?

Issue:     
 Can we utilize two wire control on the electrically held 8903 type L lighting contactors 

Product Line:
8904 lighting contactors

Environment:
Products sold and used in the United States

Cause:
Wiring an electrically held contactor for two wire control

Resolution:
The electrically held contactors do not need two wire control since they have just one coil.


CTA-ID : 2052300