What needs to be done when prompted PrtF Fault on display after installing replacement MCB and/or Power Board?

Need to Hit Enter, select Power ID (For 18-Pulse CPD=IP00, E-Flex =IP00, Open or Custom Enclosed units = IP20, etc.) Set for IPxx and hold Ent key for 2 seconds.