Is there a low consumption DC coil for Everlink D-Line Contactors?

Issue:
Is there a low consumption DC coil for Everlink D-Line Contactors?

Product Line:
TeSys D Contactors

Environment:
Products sold and used in the United States

Cause:
Low consumption requirements

Resolution:
No, but the DC coils for the Everlink or LC1D**A contactors do have a lower consumption than the older DC coils. The inrush consumption for these is 19W and sealed is 7.5W.
Average consumption on DC coils for Non Everlink LC1D40 to LC1D65 D-Line contactors is 22W