Technical FAQs

Ask a Question

What is the wind rating for Square D outdoor NEON 3R medium voltage switchgear?

Square D medium voltage switchgear has not been tested for wind loading. Calculations have been done for an HVL NEMA 3R switch enclosure with 150mph wind. These calculations prove that the enclosure can withstand this wind loading when anchored properly. These calculations would apply to all outdoor medium voltage switchgear.

CTA-ID : 2051442
Was this helpful?
What can we do to improve the information ?