What is the conductor (or wire) temperature rating (or range) of the lugs for General Duty, Heavy Duty and Double Throw safety switches?

Issue:
Product design features

Product Line:
Safety Switches

Environment:
Lug temperature ratings

Cause:
Wire Installation

Resolution:
For the General Duty, Heavy Duty and Double Throw safety switch lugs, they are ALL UL listed to accept 60 or 75 degree C wires on 30 - 100 ampere switches and 75 degree C wires on 200 - 1200 ampere switches.