Are any of Square D Safety Switches(GD, HD or DT) available with a 200% rated neutral capacity?

Issue;
Product Design Features

Product Line:
General Duty, Heavy Duty and Double Throw Safety Switches

Environment:
Solid Neutral Assembly

Cause:
Application

Resolution:
The ONLY safety switches that are available for use with a 200% rated neutral are shown below. The rest DO NOT have the ability for a 200% rated neutral.

1) The General Duty 200amp Series F1 ONLY and requires (1) additional neutral kit SN20A and the neutral jumper kit SN20NI.
2) The Heavy Duty 200amp Series F5 & F6 ONLY and requires (1) additional neutral kit SN20A and the neutral jumper kit  SN20NI.
3) The Double Throw Switches do NOT have any 200% rated neutral capability. 



 