Technical FAQs

Ask a Question

Can the QONQ 300 Ampere and 400 Ampere Load Centers, QONQ30LS400 QONQ42LS400 QONQ42MS300 QONQ42MS400, be installed in a MH-WP, NEMA Type 3R, Rainproof enclosure?

Issue:
Selection

Product Line:
QO Load Center

Environment:
300A and 400A QONQ

Cause:
Selection

Resolution:
The 300A and 400A QONQ Load Center Interiors are UL Listed only for use in NEMA Type 1 enclosures. For a NEMA Type 3R application, consider using the NQ panelboard product line.


CTA-ID : 2051028
Was this helpful?
What can we do to improve the information ?