When using a 225A NF interior NF442L2C in an MH56 box, is it possible to use a vented cover such as an NC56VS?

Issue:
When using a 225A NF interior NF442L2C in an MH56 box, is it possible to use a vented cover such as an NC56VS?  

Product Line:
Panelboards.

Environment:
Products sold in the United States.

Cause:
Product features.

Resolution:
No. The 225A NF panels cannot use the vented covers. Use the NC56S or NC56F covers for this application.


CTA-ID : 2050511