Is a two pole 100% rated P Frame breaker available? Catalog number would be similar to PGL26120C.

The two pole P Frame breakers cannot be 100% rated. Use a 100% rated three pole breaker such as a PGL36120CU31A for the application (depending on needed AIC rating), and use two poles.