Does Schneider Electric offer optional lugs for EDB, EGB, and EJB circuit breakers?

Issue:
Does Schneider Electric offer optional lugs for EDB, EGB, and EJB circuit breakers?

Product Line:
EDB, EGB, EJB type circuit breakers

Environment:
Panel boards

Cause:
Circuit breakers sometimes need lugs for different wire sizes than the standard lug permits.

Resolution:
AL100FD can be factory installed using suffix LH like EDB34020LH for 15-30 amp breakers and is standard on 35 - 125 amp breakers. Wire range (1) #14–#2/0 AWG Al/Cu
AL30FD is standard on 15-30 A EDB breakers.  Wire range:  (1) #14–#6 AWG Al/Cu
CU100FD is still a field installable option for 15-125 amp breakers.  Wire range (1) #14–#1/0 AWG Cu
VC100FD is an optional aluminum compression lug for all 15-125 amp breakers.  Wire range #8–#1/0 AWG Al/Cu
CVC100FD is an optional copper compression lug for all 15-125 amp breakers. Wire range #6-#1/0 Cu
 