What Class of fuse does the D226NR safety switch accept?

Issue:
Product design feature

Product Line:
General Duty Safety Switches 

Cause:
Fuse type

Resolution:
This switch accepts Class H or K fuses as standard. Options include Class R fuses (field install Class R Fuse Kit DRK600). With Class H or K fuses installed, the switch is UL listed for use on systems with up to 10,000 RMS Symmetrical Amperes available fault current. With Class R fuses (and DRK600 fuse kit installed) the switch is UL listed for use on systems with up to 100,000 RMS Symmetrical Amperes available fault current.

NOTE: DO NOT USE RENEWABLE LINK FUSES IN SQUARE D SAFETY SWITCHES. The use of renewable link fuses may adversely affect user safety, impair reliability and will void the warranty.