Can a 100% rated HDL or JDL circuit breaker be installed into a JD250S enclosure?

Issue:
Application

Product Line:
Circuit Breaker Enclosures

Cause:
Application

Resolution:
This enclosure has been tested and listed for use ONLY with standard rated (80%), HDL or JDL, 3 pole circuit breakers.
NOTE: The voltage is limited to 480Vac maximum. The SCCR is limited to 18K rms symmetrical amperes at 240Vac or 480Vac. Copper conductors (75 Degree C) MUST be used (aluminum conductors are not acceptable).