Is an NQ panel available with single bus construction for 120V and neutral only?

Issue:
Is an NQ panel available with single bus construction for 120V and neutral only?

Product Line:
Panelboards.

Environment:
Products sold in the United States.

Cause:
Selection.

Resolution:
Yes. A single phase panel is available with both L1 and L2 buses tied together as factory assembled and UL approved as such. In Product Selectors, customer must use notes to engineering to obtain a through feed bus panel and Peru will cable between the through feed lugs, making all breakers at the same potential. Will be labeled properly as a UL listed 120V panel.