Technical FAQs

Ask a Question

Can a J Frame breaker with a Motor Operator be installed in an I-Line panelboard?

Issue:
Can a J Frame breaker with a Motor Operator be installed in an I-Line panelboard?

Product Line:
I Line Panelboard

Environment:
Accessory

Cause:
Installation clarification


Resolution:
Yes, in I-Line panels that will accept J Frame breakers. However, the Motor Operator mandates use of a 4 piece trim with  NO door, since a door will not close over a motor operator.


CTA-ID : 2050379
Was this helpful?
What can we do to improve the information ?