What is the current density of standard bus for HVL switchgear?

600A Aluminum Bus 1/4`` x 2.5`` 960A per sq in
600A Copper Bus 1/4`` x 2`` 1200A per sq in
1200A Copper Bus Two - 1/4`` x 3`` 800A per sq in