What is the short current cIrcuit rating for the 8536 starters?<br /><br />

The following ratings are required by UL for UL listing purposes and will apply to the starter only. Horsepower ratings are 480v 3phase.

Horsepower SCCR (A)

>1 thru 50 5,000
51 thru 200 10,000
201 thru 400 18,000
401 thru 600 30,000