Technical FAQs

Ask a Question

How do you wire the shunt trip on a EDB breaker?

Product Line:
PowerPact E frame

Applies to EDB, EGB, and EJB with shunt trip accessory installed.

Use terminals 6 & 7 on the breaker to wire the shunt trip. Because it is AC, it is polarity insensitive. The other terminals are not operative.

For more information please see instruction bulletin 48840-097-02.

CTA-ID : 2049413
Was this helpful?
What can we do to improve the information ?