What lugs are included in Lug Kit CMELK4, and what are their mounting torque specification?

Issue:
Product Feature

Product Line:
Metering Accessory

Cause:
Clarification

Resolution:
CMELK4 is the Catalog Number for a Lug Kit that includes a quantity of four (4) TA-600-2N, ILSCO Mechanical Lugs.
Wire range of the Ilsco TA-600-2N lug is #2 AWG to 600 kcmil AL/CU, and torque value for wire binding screws is 375 Lb-In (inch-pounds).
Lug Mounting Hardware as used in most Square D Metering Equipment includes (2) 1/2``-13 Keps Nuts (part number: 23427-02800), and (2) Flat Washers(part number: 23601-00282) per Lug. Bag Assy: 40562-118-50 that includes (6) Keps Nuts and (6) Flat Washers.
Torque value for 1/2``-13 Keps Nut is listed on each units wiring diagram, typically: 300 Lb-In (inch-pounds).