What amperage of QO tenant breaker can be used with the EZM125QOA tenant breaker adapter kit?

Issue:
Product Features

Product Line:
EZM Metering

Environment:
Tenant breaker size

Cause:
Application

Resolution:
Due to the Short Circuit Current Ratings(SCCRs) of the EZM metering equipment, when the EZM125QOA adapter kit is used, it will accept ONLY 2 POLE QO (40 to 125 amp), QO-VH (40-60 amp) or QOH (40-60amp) tenant circuit breakers.

The installation instructions for the EZM125QOA will state "USE ONLY 2 POLE 125A MAXIMUM CIRCUIT BREAKER QO, QO-VH OR QOH". BUT for the SCCR of the EZM metering equipment, the above must be followed.

NOTE: The EZM125QOA will NOT accept QO-GFI or QO-AFI breakers.