What is the catalog number for a plug on Surge Arrestor for NQOD and NQ panelboards?

Issue:
Selection of appropriate plug on surge arrestor for NQOD and NQ panelboards.

Product Line:
PTFDS - FD Enclosure Systems

Environment:
NQOD/NQ panelboards sold and supported in the USA.

Cause:
Selection and application of appropriate plug on surge arrestor for NQOD and NQ panelboards.

Resolution:
Use QO2175SB for 120/240 Vac Single Phase 3 wire NQOD panelboards. Two adjacent branch spaces are required for mounting.
Use two QO2175SB for 208Y/120 Vac Three Phase 4 wire NQOD panelboards only. Do not use on 240/120 Vac Three Phase 4 wire applications.