Can the QMB800T6 Class T fuse adapter kit be adjusted to accept a 400A class T fuse?

Issue:
Fuse Kit

Product Line:
QMB Branch Switches

Environment;
Class T fuses

Cause:
Application

Resolution:
No. the Kit QMB800T6 is designed to adapt QMB type fusible switches to longer length and higher amperage Class T fuses. The 400A fuses are shorter, and cannot be used with the QMB800T6.