Are trim and dead front screws for NQ, NQOD & NF panels, up to 250 amps, the same type of screw?

Issue:
Are trim and deadfront screws for NQOD, NQ and NF panels, up to 250A maximum, the same type of screw?

Product Line:
Circuit breaker panelboards and accessories sold and supported in the USA.

Environment:
Maintenance

Cause:
Determine of type of screws used in circuit breaker panelboards.

Resolution:
NQ and NQODmono flat (225A and less) and NF (250A and less) trims = 40205-130-01K.
NQ and NQOD and NF trims for 400A and higher = LP9502
All NQ, NQOD and NF hinged trims = LP9502 and 40205-130-01K
All TVSS trims, equipment space trims and contactor covers = LP9502
All deadfront screws = 80025-067-01




 