Does equipment space kit NQES18 go at the top or the bottom of his panel?

Issue:
Does equipment space kit NQES18 go at the top or the bottom of his panel?

Product Line:
NQ Panelboard

Environment:
Installation

Cause:
Clarification

Resolution:
NQES18 equipped space accessory mounts at the OPPOSITE end of the Main breaker , or Main lugs. The cover will need to be ordered separate and the part number is determined by the cable entry direction , Top , or Bottom.

For Top fed interiors order Surface trim MHC2018CSB, or Flush trim MHC2018CFB
For Bottom fed interiors order Surface trim MHC2018CST, or Flush Trim MHC2018CFT