Is there a DC trip curve available for QO or QOB type breakers?

The trip curves are the same as for AC. For 48V DC rated QO breakers, on the existing trip curves, the thermal half of the curve remains at the same value, but the magnetic part shifts to the right of the existing points by a factor of x 1.2.