Is a single pole I-Line circuit breaker available that is rated at 600 Volts?

Issue:
Is a single pole I-Line circuit breaker available that is rated at 600 Volts?

Product Line:
I line panelboards.

Environment:
Products sold in the United States.

Cause:
Product availability.

Resolution:
No. The single pole I-Line type breakers are limited to 277 Volts maximum per pole. If there is a requirement for a single pole 600v breaker, it is advisable to use a two pole FA26020AB or similar breaker, and only use one pole.