Does the neutral bar on a factory assembled NQ panel come bonded to the metal box?

No. The panel neutrals are normally not bonded to ground when shipped. Bonding the neutral to ground is usually done on a service entrance panel only.

If the neutral needs to be bonded to the box on an NQ panel, use bonding straps. Catalog numbers are: For the 100 and 225 amp is 80122-269-50. For the 400 and 600 amp is 80122-270-50. Kit includes lugs and required screws.