What are the NQ panelboard main lug wire ranges and torque values?

Issue:
What are the NQ panelboard main lug wire ranges and torque values?

Product Line:
Panelboards

Environment:
NQ Panelboards

Cause:
What are the NQ panelboard main lug wire ranges and torque values?

Resolution:
 
NQ Panelboard Main Lug Wire Ranges and Torque Values
  100 A 225 A 400 A 600 A
Aluminum Main Lugs and Bus (1) 6-2/0 CU-AL; 45-50 lbs-in (1) 6-350 kcmil CU-AL; 275 lbs-in (1) 1/0-750 kcmil or (2) 1/0-350 kcmil CU-AL; 275-300 lbs-in (2) 1/0-750 kcmil or (3) 6-250 kcmil CU-AL; 275 lbs-in
Copper Main Lugs and Bus (1) 6-2/0 CU; 100 lbs-in (1) 6-250 kcmil CU; 275 lbs-in (1) 1/0-750 kcmil or (2) 1/0-350 kcmil CU; 275-300 lbs-in (2) 1/0-750 kcmil or (3) 6-250 kcmil CU; 275 lbs-in