What enclosures are available for a PowerPact P-frame circuit breaker?


Product line:
CB Enclosure


The PowerPact P-frame breakers ( PGL, PKL, PJL, PLL ) have several enclosure options:
800A maximum options are M800S (NEMA 1), M800R (NEMA 3R), M800AWK (NEMA 12) and M800DS (NEMA 4,4X,5). The P1200 enclosures noted immediately below could also be used. 
1200A maximum options are P1200S (NEMA 1), P1200R (NEMA 3R), and P1200AWK (NEMA 12).
100% rated P frame PowerPact breakers can only be used in the P1200S, P1200R or P1200AWK, 800A maximum.

NOTE: The enclosures are marked for use with 500 KCMIL maximum conductors.