Technical FAQs

Ask a Question

Does the D326NR safety switch have a hub provision in the top endwall?

This switch is provided with a blank top endwall. For conduit entry in the top endwall, a field cut opening is required. Use B type hubs, 3`` - 4`` (B300, B350 or B400) or H type hubs, 3`` - 4`` (H300, H350 or H400).

CTA-ID : 2047760
Was this helpful?
What can we do to improve the information ?