8536SG Series A (no coil voltage given) - customer needs the armature assembly for this starter.

If your contactor or starter is a Class 8502/8536 Type SG Series A and you need to replace the armature and magnet assembly, purchase one of the following E-Coil Conversion Kits. These kits include a magnet, armature and the new electronic coil along with fusing. Replacement Series A armature/magnet kits are not generally available. If it is a 600v or jogging application, contact Control PSG.

E-Coil Conversion Kits For Series A

Class 9998 Type SG120 - 120VAC
Class 9998 Type SG208 - 208VAC
Class 9998 Type SG240 - 240VAC
Class 9998 Type SG380 - 380VAC
Class 9998 Type SG480 - 480VAC