Is there a lug option for qty 3 conductors on the 600a, NQ, main lug panelboard.

Issue:
Is there a lug option for qty 3 conductors on the 600a, NQ, main lug panelboard.

Product Line:
Panelboards.

Environment:
Products sold in the United States.

Cause:
Product features.

Resolution:
Yes, order lug kit NQALM6A, qty 3, #1/0 to 250 kcmil. Optional lug for a 600A can also be used for a 400A.